Error
Error and cause
code
[SP. PARA ERROR]
• The refresh setting of the intelligent function
module exceeded the file register capacity.
• The intelligent function module set in GX
Configurator differs from the actually mounted
module.
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• When an END instruction or a COM instruction
executed
[SP. PARA ERROR]
The intelligent function module's refresh
parameter setting is outside the available range.
■Collateral information
3301
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• When an END instruction or a COM instruction
executed
[SP. PARA ERROR]
The setting of the refresh parameter range
crosses over the boundary between the internal
user device and the extended data register (D) or
extended link register (W).
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• When an END instruction or a COM instruction
executed
[SP. PARA ERROR]
The intelligent function module's refresh
parameter are abnormal.
■Collateral information
3302
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of
another station.
3303
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
372
Corrective action
• Change the file register file for the one that
the entire target range can be refreshed.
• Check the parameter setting.
• Check the auto refresh setting.
*1
• Check the parameter setting.
• Check the auto refresh setting.
*1
Set the refresh parameter range so that it
does not cross over the boundary between
the internal user device and the extended
data register (D) or extended link register (W).
*1
Check the parameter setting.
*1
• Delete the automatic refresh setting or
other parameter setting of the intelligent
function module under control of another
CPU.
• Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of
the host CPU.
LED status,
Corresponding
CPU status
Q00J/Q00/Q01
Qn(H)
QnPH
QnPRH
LCPU
RUN: Off
ERR.:Flashing
QCPU
LCPU
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QCPU
LCPU
CPU Status:Stop
RUN: Off
Q00/Q01
ERR.:Flashing
Qn(H)
QnPH
CPU Status:Stop
CPU
QnU
QnU
QnU

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents