Mitsubishi Electric Q26UD(E)HCPU User Manual page 462

Melsecq series
Hide thumbs Also See for Q26UD(E)HCPU:
Table of Contents

Advertisement

Number
Name
Online module
SM236
change complete
flag
Device range
SM237
check inhibit flag
No. 1 CPU reset
SM240
flag
No. 2 CPU reset
SM241
flag
No. 3 CPU reset
SM242
flag
No. 4 CPU reset
SM243
flag
No. 1 CPU error
SM244
flag
No. 2 CPU error
SM245
flag
No. 3 CPU error
SM246
flag
No. 4 CPU error
SM247
flag
Max. loaded I/O
SM250
read
460
Meaning
OFF: Online module
• This relay is on only for one scan after
change
completion of online module change.
incomplete
• This relay can be used only in the scan
ON: Online module
execution type program. (for host CPU)
change complete
Selects whether to check a device range
OFF: Device range
during execution of the BMOV, FMOV or
checked
DFMOV instruction (only when the
ON: Device range not
conditions for subset processing are
checked
established).
• Turns off when CPU No.1 is reset.
OFF: No. 1 CPU reset
• Turns on while CPU No.1 is being reset
cancel
(including the case where the CPU
ON: No. 1 CPU
module is removed from the base unit).
resetting
The other CPUs are also put in reset
status.
Reset status
This relay is always off. (reset status)
• Turns off when CPU No.2 is reset.
OFF: No. 2 CPU reset
• Turns on while CPU No.2 is being reset
cancel
(including the case where the CPU
ON: No. 2 CPU
module is removed from the base unit).
resetting
"MULTI CPU DOWN" (error code:
7000) is detected on the other CPUs.
• Turns off when CPU No.3 is reset.
OFF: No. 3 CPU reset
• Turns on while CPU No.3 is being reset
cancel
(including the case where the CPU
ON: No. 3 CPU
module is removed from the base unit).
resetting
"MULTI CPU DOWN" (error code:
7000) is detected on the other CPUs.
• Turns off when CPU No.4 is reset.
OFF: No. 4 CPU reset
• Turns on while CPU No.4 is being reset
cancel
(including the case where the CPU
ON: No. 4 CPU
module is removed from the base unit).
resetting
"MULTI CPU DOWN" (error code:
7000) is detected on the other CPUs.
• This relay is off when CPU No.1 is
OFF: No. 1 CPU
normal (including the case where a
normal
continuation error has occurred).
ON: No. 1 CPU during
• This relay is on when CPU No.1 has a
stop error
stop error.
• This relay is on when CPU No.2 is
OFF: No. 2 CPU
normal (including the case where a
normal
continuation error has occurred).
ON: No. 2 CPU during
• This relay is on when CPU No.2 has a
stop error
stop error.
• This relay is off when CPU No.3 is
OFF: No. 3 CPU
normal (including the case where a
normal
continuation error has occurred).
ON: No. 3 CPU during
• This relay is on when CPU No.3 has a
stop error
stop error.
• This relay is off when CPU No.4 is
OFF: No. 4 CPU
normal (including the case where a
normal
continuation error has occurred).
ON: No. 4 CPU during
• This relay is on when CPU No.4 has a
stop error
stop error.
When this relay turns on from off, the
OFF: Ignored
largest I/O number among those of the
ON: Read
mounted modules is read into SD250.
Set by
Explanation
(When Set)
S (When
online
module
change is
complete)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
S (Status
change)
Corresponding
Corresponding
ACPU
M9
New
U
New
Q00/Q01
New
New
Q00/Q01
New
Q00/Q01
New
New
Q00/Q01
New
Q00/Q01
New
Q00/Q01
New
New
U
New
CPU
QnPH
*6
QnU
LCPU
*1
*1
Qn(H)
QnPH
*7
QnU
LCPU
*1
*1
Qn(H)
QnPH
*7
QnU
*1
*1
Qn(H)
QnPH
*7
QnU
*1
Qn(H)
QnPH
*5
QnU
*1
*1
Qn(H)
QnPH
*7
QnU
LCPU
*1
*1
Qn(H)
QnPH
*7
QnU
*1
*1
Qn(H)
QnPH
*7
QnU
*1
Qn(H)
QnPH
*5
QnU
Qn(H)
QnPH
QnPRH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents