Error
Error and cause
code
[SFC PARA. ERROR]
• The parameter setting is illegal.
• The block 0 does not exist although "Autostart
Block 0" was selected in the SFC tab in "PLC
Parameter".
3200
■Collateral information
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• STOP  RUN
[SFC PARA. ERROR]
The block parameter setting is illegal.
■Collateral information
• Common information: File name
3201
• Individual information: Parameter number
■Diagnostic timing
• STOP  RUN
[SFC PARA. ERROR]
The number of step relays specified in the device
setting of "PLC Parameter" is less than that used
in the program.
3202
■Collateral information
• Common information: File name
• Individual information: Parameter number
■Diagnostic timing
• STOP  RUN
[SFC PARA. ERROR]
Other than "Scan" and "Wait" is set for "Execute
Type" in the Program tab of "PLC Parameter".
■Collateral information
3203
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
[SP. PARA ERROR]
The start I/O number in the intelligent function
module parameter set on GX Configurator differs
from the actual I/O number.
■Collateral information
3300
• Common information: File name/Drive name
• Individual information: Parameter number
■Diagnostic timing
• At power-on/At reset/STOP  RUN
Corrective action
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value, and
correct them as necessary.
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value, and
correct them as necessary.
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value, and
correct them as necessary.
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value, and
correct them as necessary.
*2
Check the parameter setting.
*1
APPENDICES
LED status,
Corresponding
CPU status
CPU
Q00J/Q00/Q01
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
QnU
LCPU
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
RUN: Off
Qn(H)
ERR.:Flashing
QnPH
QnPRH
CPU Status:Stop
Qn(H)
RUN: Off
QnPH
ERR.:Flashing
QnPRH
QnU
CPU Status:Stop
LCPU
RUN: Off
ERR.:Flashing
QCPU
LCPU
CPU Status:Stop