Error
Error and cause
code
[SINGLE PS. DOWN]
The power supply voltage of either of redundant
power supply modules on the redundant base unit
dropped.
■Collateral information
1510
• Common information: Base No./Power supply
No.
• Individual information: -
■Diagnostic timing
• Always
[SINGLE PS. ERROR]
On the redundant base unit, the one damaged
redundant power supply module was detected.
■Collateral information
• Common information: Base No./Power supply
1520
No.
• Individual information: -
■Diagnostic timing
• Always
*2
[BATTERY ERROR
]
• The battery voltage in the CPU module has
dropped below stipulated level.
• The lead connector of the CPU module battery
is not connected.
• The lead connector of the CPU module battery
1600
is not securely engaged.
■Collateral information
• Common information: Drive Name
• Individual information: -
■Diagnostic timing
• Always
*2
[BATTERY ERROR
]
Voltage of the battery on memory card has
dropped below stipulated level.
■Collateral information
1601
• Common information: Drive Name
• Individual information: -
■Diagnostic timing
• Always
[FLASH ROM ERROR]
The number of writes to flash ROM (standard
ROM and system securement area) exceeds
100,000 times. (Number of writes > 100,000
times)
1610
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• When writing to ROM
[BUS TIMEOUT ERR.]
An error was detected on the system bus.
• Self-diagnosis error of the system bus
• Self-diagnosis error of the CPU module
1700
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• Always
[UNIT BUS ERROR]
• An error was detected on the system bus.
• An error was detected in the connected module.
■Collateral information
1710
• Common information: Module No. (Slot No.)
• Individual information: -
■Diagnostic timing
• Always
Corrective action
Check the power supplied to the redundant
power supply modules mounted on the
redundant base unit.
The cause is a hardware failure of the
redundant power supply module. Please
consult your local Mitsubishi representative.
• Change the battery.
• Engage the battery connector when a
program memory, standard RAM, or the
back-up power function is used.
• Check the lead connector of the CPU
module for looseness. Firmly engage the
connector if it is loose.
Change the battery.
Change the CPU module.
Reset the CPU module and run it again. If the
same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your local
Mitsubishi representative.
• Disconnect the extension block.
• Do not use the LA1S extension base unit.
• Reset the CPU module and run it again. If
the same error code is displayed again, the
cause is a hardware failure of the CPU
module, I/O module, intelligent function
module, END cover, branch module, or
extension module. Please consult your
local Mitsubishi representative.
APPENDICES
LED status,
Corresponding
CPU status
CPU
RUN: On
Qn(H)
ERR.:On
QnPH
QnPRH
CPU Status:Continue
QnU
RUN: On
Qn(H)
ERR.:On
QnPH
QnPRH
CPU Status:Continue
QnU
RUN: On
ERR.:Off
QCPU
LCPU
CPU Status:Continue
Qn(H)
RUN: On
QnPH
ERR.:Off
QnPRH
QnU (except
CPU Status:Continue
QnUDV)
RUN: On
ERR.:On
QnU
LCPU
CPU Status:Continue
RUN: Off
ERR.:Flashing
LCPU
CPU Status:Stop
RUN: Off
ERR.:Flashing
LCPU
CPU Status:Stop
A