Overview of Alarms
SINAMICS-Alarms
Remedy:
- check the DRIVE-CLiQ connection.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
236802
<location>Hub: Time slice overflow
Message
%1
value:
Drive object:
A_INF, B_INF, HUB, S_INF, SERVO, TM41, VECTOR
Reaction:
A_INFEED: OFF2 (NONE)
SERVO: NONE
VECTOR: NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
A time slice overflow has occurred on the DRIVE-CLiQ Hub Module.
Fault value (r0949, interpret decimal):
xx: Time slice number xx
Remedy:
- reduce the current controller frequency.
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
236804
<location>Hub: Checksum error
Message
%1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
A checksum error (CRC) occurred when the program memory on the DRIVE-CLiQ Hub Module was
read out.
Alarm value (r2124, interpret hexadecimal):
Difference between the checksum at POWER ON and the current checksum.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- Replace DRIVE-CLiQ Hub Module.
236805
<location>Hub: EEPROM checksum incorrect
Message
%1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal parameter data on the DRIVE-CLiQ Hub Module are incorrect.
Alarm value (r2124, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
- check whether the permissible ambient temperature for the component is maintained.
- Replace DRIVE-CLiQ Hub Module.
236820
<location>Hub DRIVE-CLiQ: Telegram error
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from Control Unit to DRIVE-CLiQ Hub Module in question.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 01 hex = 1 dec:
Checksum error (CRC error).
xx = 02 hex = 2 dec:
Telegram is shorter than specified in the length byte or in the receive list.
2-978
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
© Siemens AG 2009 All Rights Reserved
03/2009