03/2009
201488
<location>Topology: Comparison EnDat encoder missing in the actual
topology
Message
Component number: %1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected an EnDat encoder in the target topology that is not available
in the actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- re-configure the drive belonging to the encoder in the commissioning software project (encoder con-
figuration) and download the new configuration to the drive unit.
- delete the drive belonging to the encoder in the commissioning software project and download the
new configuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
201489
<location>Topology: Comparison motor with DRIVE-CLiQ missing in the
actual topology
Message
Component number: %1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a motor with DRIVE-CLiQ in the target topology that is not
available in the actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- re-configure the drive belonging to this motor in the commissioning software project and download
the new configuration to the drive unit.
- re-configure the drive belonging to this motor in the commissioning software project and download
the new configuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the motor is working properly.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
201505
<location>BICO: Interconnection cannot be established
Message
Parameter: %1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A PROFIdrive telegram has been set (p0922).
An interconnection contained in the telegram was not able to be established.
Fault value (r0949, interpret decimal):
Parameter receiver that should be changed.
Remedy:
Establish another interconnection.
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-669