Siemens Sinumerik 840D sl Diagnostic Manual page 979

Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

03/2009
xx = 03 hex = 3 dec:
Telegram is longer than specified in the length byte or in the receive list.
xx = 04 hex = 4 dec:
The length of the receive telegram does not match the receive list.
xx = 05 hex = 5 dec:
The type of the receive telegram does not match the receive list.
xx = 06 hex = 6 dec:
The address of the component in the telegram and in the receive list do not match.
xx = 07 hex = 7 dec:
A SYNC telegram is expected - but the receive telegram is not a SYNC telegram.
xx = 08 hex = 8 dec:
No SYNC telegram is expected - but the receive telegram is one.
xx = 09 hex = 9 dec:
The error bit in the receive telegram is set.
xx = 10 hex = 16 dec:
The receive telegram is too early.
Remedy:
- carry out a POWER ON.
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
236835
<location>Hub DRIVE-CLiQ: Cyclic data transfer error
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from Control Unit to DRIVE-CLiQ Hub Module in question. The
nodes do not send and receive in synchronism.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 21 hex = 33 dec:
The cyclic telegram has not been received.
xx = 22 hex = 34 dec:
Timeout in the telegram receive list.
xx = 40 hex = 64 dec:
Timeout in the telegram send list.
Remedy:
- carry out a POWER ON.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
236836
<location>Hub DRIVE-CLiQ: Send error for DRIVE-CLiQ data
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
DRIVE-CLiQ communication error from Control Unit to DRIVE-CLiQ Hub Module in question. Data
were not able to be sent.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 41 hex = 65 dec:
Telegram type does not match send list.
Remedy:
Carry out a POWER ON.
236837
<location>Hub DRIVE-CLiQ: Component fault
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-979