Remedy:
Carry out a POWER ON (power off/on) for all components.
If the error occurs after the drive sampling times were adjusted, and if a TM31 module is being used,
the sampling times (p0115, p4099) should be set as integer multiples to the drive clock cycles (p0115).
201954
<location>CU DRIVE-CLiQ: Synchronization unsuccessful
Message
%1
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
After the drive system is powered up, the synchronization between the basic clock cycle, DRIVE-CLiQ
clock cycle and application clock cycle was started and was not able to be successfully completed.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
1. Ensure perfect functioning of the DRIVE-CLiQ.
2. Initiate a new synchronization, e.g. as follows:
- remove the PROFIBUS master and re-insert again.
- restart the PROFIBUS master.
- power down the Control Unit and power it up again.
- press the Control Unit reset button.
- reset the parameter and download the saved parameters (p0009 = 30, p0976 = 2).
201955
<location>CU DRIVE-CLiQ: Synchronization DO not completed
Message
%1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
After the drive system is powered up, the synchronization between the basic clock cycle, DRIVE-CLiQ
clock cycle and application clock cycle was started but was not completed within the selected time
tolerance.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
Carry out a POWER ON (power off/on) for all components of the DO.
202000
<location>Function generator: Start not possible
Message
-
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The function generator has already been started.
Remedy:
Stop the function generator and restart again if necessary.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
See also: p4800 (Function generator control)
202005
<location>Function generator: Drive does not exist
Message
%1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive object specified for connection does not exist.
See also: p4815 (Function generator drive number)