Overview of Alarms
NCK alarms
Definitions:
In the NCK MD or in the S7 F parameters, the same PROFIsafe address has been parameterized for
the F modules parameterized in the specified machine data. Therefore, no clear communication link
is possible between F master and F slave.
Reaction:
Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Check and correct the S7 F parameterization and NCK MD.
Program Con-
Switch control OFF - ON.
tinuation:
27225
PROFIsafe: slave %1, configuration error %2
Parameters:
%1 = PROFIBUS slave address
%2 = Configuration error
Definitions:
An error occurred during the evaluation of the S7 PROFIBUS configuration for the specified slave.
This is further specified in alarm parameter %2.
%2 = PRM header: the PRM telegram for this slave could not clearly be interpreted.
Reaction:
Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Check and correct the S7 PROFIBUS configuration.
Program Con-
Switch control OFF - ON.
tinuation:
27240
PROFIsafe: DP M not running up, DP info: %1
Parameters:
%1 = Current information from the DP interface NCK-PLC
Definitions:
There is no DP configuration available to the NCK after the time specified via the MD
$MN_PLC_RUNNINGUP_TIMEOUT.
Reaction:
Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
- Increase MD $MN_PLC_RUNNINGUP_TIMEOUT
- Check the PLC operating status.
- Check the PLC operating system software version.
- Delete the F parameterization in the NCK MD.
Program Con-
Switch control OFF - ON.
tinuation:
27241
PROFIsafe: DP M version different, NCK: %1, PLC: %2
Parameters:
%1 = DP interface version of the NCK
%2 = DP interface version of the PLC
Definitions:
The NCK and PLC components have different implementations of the DP interface. The F communi-
cation cannot be initialized.
Reaction:
Mode group not ready.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
- Check the PLC operating system and NCK software versions.
- Upgrade the PLC operating system.
- Delete the NCK F parameterization.
2-440