03/2009
26266
[Channel %1: ] Block %2: The protection area with the name %3 was
programmed several times.
Parameters:
%1 = Channel number
%2 = Block number
%3 = Name of protection area
Definitions:
The name of a protection area was programmed several times (e.g, during the function call PROTA).
Reaction:
Correction block is reorganized.
Alarm display.
NC Stop on alarm.
Remedy:
Indicate each required name of a protection area only once.
Program Con-
Clear alarm with NC START or RESET key and continue the program.
tinuation:
26268
[Channel %1: ] Block %2: Protection area %3 has not been assigned an
interface bit
Parameters:
%1 = Channel number
%2 = Block number
%3 = Name of protection area
Definitions:
An attempt was made to preactivate a protection area to which no interface bit was assigned. Protec-
tion areas can be preactivated only if an interface bit was defined in $NP_BIT_NO[..] through which
switchover between activated and deactivated state is possible in a preactivated protection area.
Reaction:
Correction block is reorganized.
Alarm display.
NC Stop on alarm.
Remedy:
Assign an interface bit to the protection area or select another activation mode (active / inactive).
Program Con-
Clear alarm with NC START or RESET key and continue the program.
tinuation:
26270
[Channel %1: ] Block %2: Invaid activation parameter during the PROTA
function call
Parameters:
%1 = Channel number
%2 = Block number
Definitions:
The activation parameter of the PROTA function contains an invalid value.
Only the following values are permitted:
"A" or "a" (= activated)
"I" or "i" (= inactivated)
"P" or "p" (= preactivated)
"R" or "r" (= take over activation state from protection area definitions)
Reaction:
Correction block is reorganized.
Alarm display.
NC Stop on alarm.
Remedy:
Indicate a valid activation parameter ("A", "a", "I", "i", "P", "p" , "R", "r").
Program Con-
Clear alarm with NC START or RESET key and continue the program.
tinuation:
26272
[Channel %1: ] Block %2: The contents (%3) of parameter
$NP_INIT_STAT[%4] are invalid
Parameters:
%1 = Channel number
%2 = Block number
%3 = Programmed state
%4 = Index of parameters
Definitions:
An invalid activation state was indicated for a protection area.
Only the following values are permitted:
"A" or "a" (= activated)
"I" or "i" (= inactivated)
"P" or "p" (= preactivated)
Reaction:
Correction block is reorganized.
Alarm display.
NC Stop on alarm.
© Siemens AG, 2009. All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
NCK alarms
2-399