Overview of Alarms
SINAMICS-Alarms
201036
<location>ACX: Parameter back-up file missing
Message
%1
value:
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a parameter back-up file associated with a drive
object cannot be found. Neither a PSxxxyyy.ACX, a PSxxxyyy.NEW nor a PSxxxyyy.BAK parameter
back-up file exists on the CompactFlash card for this drive object.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved the project data using the commissioning software, carry out a new download for
your project. Save using the function "Copy RAM to ROM" or with p0977 = 1 so that all of the param-
eter files are again completely written to the CompactFlash card.
If you have not saved the project data, then first commissioning of the system has to be carried out
again.
201037
<location>ACX: Re-naming the parameter back-up file unsuccessful
Message
%1
value:
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
Re-naming after saving a parameter back-up file on the CompactFlash card or in the volatile memory
was unsuccessful.
One of the parameter back-up files to be re-named had the "read only" attribute. The parameter back-
up files are saved on the CompactFlash card in the directory \USER\SINAMICS\DATA.
It is possible that the CompactFlash card is defective.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file names PSxxxyyy.* or CAxxxyyy.* or CCxxxyyy.*
yyy = 000 --> consistency back-up file
yyy = 099 --> PROFIBUS parameter back-up file PSxxx099.*
Byte 2: xxx in the file name PSxxxyyy.*
xxx = 000 --> data save started with p0977 = 1
xxx = 010 --> data save started with p0977 = 10
xxx = 011 --> data save started with p0977 = 11
xxx = 012 --> data save started with p0977 = 12
Byte 4, 3:
Only for internal Siemens troubleshooting.
Remedy:
- check whether one of the files to be overwritten has the attribute "read only" and change this file
attribute to "writable". Check all of the files (PSxxxyyy.*, CCxxxyyy.*, CAxxxyyy.*) that belong to drive
yyy designated in the fault value.
- replace the CompactFlash card.
201038
<location>ACX: Loading the parameter back-up file unsuccessful
Message
%1
value:
Drive object:
All objects
Reaction:
A_INFEED: NONE (OFF2)
SERVO: NONE (OFF1, OFF2, OFF3)
VECTOR: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
2-636
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
© Siemens AG 2009 All Rights Reserved
03/2009