Overview of Alarms
SINAMICS-Alarms
Remedy:
- check whether the fan is running.
- check the fan elements
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05003 has been undershot.
230037
<location>Power unit: Rectifier overtemperature
Message
%1
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature in the rectifier of the power unit has exceeded the permissible temperature limit.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- line supply phase failure.
Fault value (r0949, interpret decimal):
Temperature [1 bit = 0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- check the line supply phases.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05004 has been undershot.
230038
<location>Power unit: Capacitor fan monitoring
Message
%1
value:
Drive object:
B_INF
Reaction:
NONE
Acknowledge:
NONE
Cause:
The capacitor fan signals a fault.
Remedy:
Replace the capacitor fan in the power unit.
230039
<location>Power unit: Failure capacitor fan
Message
%1
value:
Drive object:
B_INF
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
The capacitor fan has failed.
Remedy:
Replace the capacitor fan in the power unit.
230040
<location>Power unit: Undervolt 24 V
Message
%1
value:
Drive object:
All objects
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Failure of the 24 V power supply for the power unit.
- the 16 V threshold was undershot for longer than 3 ms.
Fault value (r0949, interpret decimal):
24 V voltage [1 bit = 0.1 V].
Remedy:
Check the 24 V DC voltage supply to power unit.
2-836