03/2009
Remedy:
Adapting the topologies:
- change over the actual topology to match the target topology.
- download the target topology that matches the actual topology (commissioning software).
Note:
In the software, a Double Motor Module behaves just like two separate DRIVE-CLiQ nodes. If a Dou-
ble Motor Module is re-inserted, this can result in several differences in the actual topology.
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
201451
<location>Topology: Target topology is invalid
Message
%1
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
An error was detected in the target topology.
The target topology is invalid.
Fault value (r0949, interpret hexadecimal):
ccccbbaa hex: cccc = index error, bb = component number, aa = fault cause
aa = 1B hex = 27 dec: Error not specified.
aa = 1C hex = 28 dec: Value illegal.
aa = 1D hex = 29 dec: Incorrect ID.
aa = 1E hex = 30 dec: Incorrect ID length.
aa = 1F hex = 31 dec: Too few indices left.
aa = 20 hex = 32 dec: component not connected to Control Unit.
Remedy:
Reload the target topology using the commissioning software.
201470
<location>Topology: Target topology ring-type connection
Message
Component number: %1, Component class: %2, Connection number: %3
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
A ring-type connection was detected when writing to the target topology.
Fault value (r0949, interpret hexadecimal):
ddccbbaa hex:
cc = connection number
bb = component class
aa = component number of a component included in the ring
Note:
Component class and connection number are described in F01375.
Remedy:
Read out the fault value and remove one of the specified connections.
Then download the target topology again using the commissioning software.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
201475
<location>Topology: Target topology duplicate connection between two
components
Message
Component number: %1, Component class: %2, Connection number1: %3, Connection number2: %4
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When writing the target topology, a duplicate connection between two components was detected.
Fault value (r0949, interpret hexadecimal):
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-665