<location>IF1: PB/PN sign-of-life synchronism not reached
Message
-
value:
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the
parameterizing telegram. Synchronization with the master sign-of-life (STW2.12 ... STW2.15) could
not be completed because the sign-of-life is changing differently to how it was configured in the Tmapc
time grid.
Remedy:
- ensure that the master correctly increments the sign-of-life in the master application clock cycle
Tmapc.
- correct the interconnection of the master sign-of-life (p2045).
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
201945
<location>PROFIBUS: Connection to the Publisher failed
Message
Fault cause: %1 bin
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
NONE
Acknowledge:
NONE
Cause:
For PROFIBUS peer-to-peer data transfer, the connection to at least one Publisher has failed.
Alarm value (r2124, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection failed.
...
Bit 15 = 1: Publisher with address in r2077[15], connection failed.
Remedy:
- check the PROFIBUS cables.
- carry out a first commissioning of the Publisher that has the failed connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
201946
<location>PROFIBUS: Connection to the Publisher aborted
Message
Fault cause: %1 bin
value:
Drive object:
A_INF, B_INF, CU_LINK, CU_S, HUB, S_INF, SERVO, TB30, TM15, TM15DI_DO, TM17, TM31,
TM41, TM54F_MA, TM54F_SL, VECTOR
Reaction:
A_INFEED: OFF1 (NONE, OFF2)
SERVO: OFF1 (NONE, OFF2, OFF3)
VECTOR: OFF1 (NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
At this drive object, the connection to at least one Publisher for PROFIBUS peer-to-peer data transfer
in cyclic operation has been aborted.
Alarm value (r2124, interpret binary):
Bit 0 = 1: Publisher with address in r2077[0], connection aborted.
...
Bit 15 = 1: Publisher with address in r2077[15], connection aborted.
Remedy:
- check the PROFIBUS cables.
- check the state of the Publisher that has the aborted connection.
See also: r2077 (PROFIBUS diagnostics peer-to-peer data transfer addresses)
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-705

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents