Siemens Sinumerik 840D sl Diagnostic Manual page 939

Hide thumbs Also See for Sinumerik 840D sl:
Table of Contents

Advertisement

03/2009
Cause:
Fault detected on the DRIVE-CLiQ component involved. Faulty hardware cannot be excluded.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 20 hex:
Error in the telegram header.
xx = 23 hex:
Receive error: The telegram buffer memory contains an error.
xx = 42 hex:
Send error: The telegram buffer memory contains an error.
xx = 43 hex:
Send error: The telegram buffer memory contains an error.
Remedy:
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
233845
<location>Encoder 3 DRIVE-CLiQ: Cyclic data transfer error
Message
Component number: %1, fault cause: %2
value:
Drive object:
All objects
Reaction:
A_INFEED: OFF2
SERVO: OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the Control Unit to the encoder involved.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 0B hex:
Synchronization error during alternating cyclic data transfer.
Remedy:
Carry out a POWER ON.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
233850
<location>Encoder 3: Encoder evaluation, internal software error
Message
%1
value:
Drive object:
All objects
Reaction:
A_INFEED: OFF2 (NONE)
SERVO: OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
VECTOR: OFF1 (IASC/DCBRAKE, NONE, OFF2, OFF3)
Acknowledge:
POWER ON
Cause:
Internal software error in the Sensor Module of encoder 3.
Fault value (r0949, interpret decimal):
1: Background time slice is blocked.
2: Checksum over the code memory is not OK.
10000: OEM memory of the EnDat encoder contains data that cannot be interpreted.
11000 - 11499: Descriptive data from EEPROM incorrect.
11500 - 11899: Calibration data from EEPROM incorrect.
11900 - 11999: Configuration data from EEPROM incorrect.
16000: DRIVE-CLiQ encoder initialization application error.
16001: DRIVE-CLiQ encoder initialization ALU error.
16002: DRIVE-CLiQ encoder HISI / SISI initialization error.
16003: DRIVE-CLiQ encoder safety initialization error.
16004: DRIVE-CLiQ encoder internal system error.
Remedy:
- replace the Sensor Module.
- if required, upgrade the firmware in the Sensor Module.
- contact the Hotline.
© Siemens AG 2009 All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
SINAMICS-Alarms
2-939

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents