03/2009
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Configure MD11352 $MN_HANDWHEEL_INPUT for a valid input for the corresponding handwheel
Program Con-
Switch control OFF - ON.
tinuation:
4700
PROFIBUS I/O: The logical slot / I/O area address %1 was not found.
Parameters:
%1 = Area address
Definitions:
For PROFIBUS/PROFINET only:
The logical slot / I/O area address was not found in MD10500 $MN_DPIO_LOGIC_ADDRESS_IN with
the stated slot / I/O area in the current STEP 7 hardware configuration.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Check the slot / I/O area address in the configuration (STEP 7, HW Config).
Program Con-
Switch control OFF - ON.
tinuation:
4702
PROFIBUS I/O: The logical slot / I/O area address %1 was not found.
Parameters:
%1 = Area address
Definitions:
For PROFIBUS/PROFINET only:
The logical slot / I/O area address was not found in MD10506 $MN_DPIO_LOGIC_ADDRESS_OUT
with the stated slot / I/O area index in the current STEP 7 hardware configuration.
Reaction:
Interface signals are set.
Alarm display.
Remedy:
Check the slot / I/O area address in the configuration (STEP 7, HW Config).
Program Con-
Switch control OFF - ON.
tinuation:
5000
Communication job not executable %1
Parameters:
%1 = Reference to which resources are no longer available.
Definitions:
The communication job (data exchange between NCK and HMI, e.g.: loading an NC part program)
cannot be executed because there is insufficient memory space. Cause: too many communication
jobs in parallel.
Reaction:
Alarm display.
Remedy:
- Reduce the number of communication jobs taking place at the same time or increase MD10134
$MN_MM_NUM_MMC_UNITS
- Restart communication job.
Please inform the authorized personnel/service department. No remedial measures are possible - the
operation triggering the alarm message has to be repeated. Clear the alarm display with Cancel.
Program Con-
Clear alarm with the Delete key or NC START.
tinuation:
6000
Memory reorganized using standard machine data
Definitions:
The memory management was not able to allocate the NC user memory with the values in the
machine data. It did not have enough memory available because the total memory available is pro-
vided as dynamic and static memory for the NC user (e.g. for macro definitions, user variables, num-
ber of tool offsets, number of directories and files etc.).
Reaction:
NC not ready.
Mode group not ready, also effective for single axes
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Redefine the NC memory structure!
A specific MD for NC user memory allocation cannot be stated to be the cause of the alarm. The MD
initiating the alarm therefore has to be determined on the basis of the default values in the machine
data by changing the user-specific memory structure step by step.
Usually, it is not just one single MD that has been set too large. Therefore it is advisable to reduce the
memory area by a certain proportion in several MDs.
© Siemens AG, 2009. All Rights Reserved
SINUMERIK 840D sl, 840Di sl, SINAMICS, Diagnostics Manual (DAsl), 03/2009
Overview of Alarms
NCK alarms
2-57