For further information refer to regional power supply standards.
Allowed isolation transformer types
The following isolation transformer types are allowed by ABB:
Delta-Wye isolation transformer (△/Y)
xx1700001318
Mains line filter
The IRC5 controller option 129-1 Prepared for CE labelling consists of a mains line
filter (3HAC024322-001) to prevent emissions to the incoming power.
A mains line filter in each robot cabinet is required for any of the below conditions:
Other types of external filters may be used, provided they are approved by regional
standards. For further information refer to regional power supply standards.
Product manual - IRC5
3HAC047136-001 Revision: M
A Primary/input
B Secondary/output
Robot system CE-labelling is required.
Robot system will be installed in an EU country.
When the mains supply is shared with a pressing machine, frequency
converter, or other large industry equipment that may cause the power supply
characteristics out of standard limits, see below.
Mains power supply is out of standard limits, like voltage variations (+10%
to -15%), frequency variations (48.5 Hz to 61.8 Hz), harmonic (5%), voltage
unbalance (2%), voltage surge, voltage dips/swells, and so on.
© Copyright 2004-2018 ABB. All rights reserved.
2 Installation and commissioning
2.5.3 Power supply system requirements
Wye-Wye isolation transformer (Y /Y)
xx1700001319
Continued
67