ABB i-bus KNX Product Manual page 118

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.6.1
Function of the logic gate
This parameter can be used to define whether a logic function or the threshold function is used.
Options
None
AND
OR
Exclusive OR
GATE
Threshold
The logic gate is not used.
The logic function AND is used. If the value 1 is present on both inputs, the result = 1. The result can be
inverted, linked with any output within the device or output on the group object Result .
The following group objects will be enabled:
Connection A
Connection B
Group object "Connection A" after bus voltage recovery
Group object "Connection B" after bus voltage recovery
Invert result
Send result on KNX
The logic function OR is used. If the value 1 is present on at least one input, the result = 1. The result
can be inverted, linked with any output within the device or output on the group object Result .
The following group objects will be enabled:
Connection A
Connection B
Group object "Connection A" after bus voltage recovery
Group object "Connection B" after bus voltage recovery
Invert result
Send result on KNX
The logic function exclusive OR is used. If different values are present on both inputs, the result = 1.
The result can be inverted, linked with any output within the device or output on the group object
Result .
The following group objects will be enabled:
Connection A
Connection B
Group object "Connection A" after bus voltage recovery
Group object "Connection B" after bus voltage recovery
Invert result
Send result on KNX
The logic function GATE is used. As long as GATE is activated, the most recent value sent to the input
(Connection B) remains as the result.
After disabling (Connection A), the value that the result had before disabling is retained. After en-
abling, the result remains unchanged until the input (Connection B) receives a new value.
The result can be inverted, linked with any output within the device or output on the group object
Result .
The following group objects will be enabled:
Connection A
Connection B
GATE disables if group object "Connection A" equals
Group object "Connection A" after bus voltage recovery
Group object "Connection B" after bus voltage recovery
Invert result
Send result on KNX
The function Threshold is used.
More information → Function Threshold, Page 85.
Data type of group object "Threshold input"
Upper threshold
Lower threshold
Change thresholds via KNX
Result if upper threshold is exceeded
Min. duration of the overshoot
Result if the input value is between the thresholds
Minimum dwell time between the thresholds
Result if lower threshold is dropped below
Min. duration of the undershoot
Update result after each overshoot/undershoot
Send result on KNX