Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.9.3.1.3
DEPENDENT PARAMETER
Disconnect output from power after
This parameter can be used to define when the output is deenergized after the upper or lower end posi-
tion is reached.
The drive deenergizes itself off by means of the integrated limit switches after reaching the upper or
lower limit position. An overrun time can be set in the parameter Delay time for drive so that the end
position is reliably reached. When the drive is switched off, the voltage remains applied for a short
time so as to move the drive to the end position in a defined manner. The position calculated in the de-
vice is the basis for determining the end position.
Options
End position, no overrun
End position + 2 % overrun
End position + 5 % overrun
End position + 10 % overrun
End position + 20 % overrun
Total travel time + 10% overrun
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual
7.9.3.1.4
DEPENDENT PARAMETER
Enable group object "Trigger reference movement"
This parameter can be used to enable the group object Trigger reference movement .
More information → Reference movement, Page 87.
Options
No
Yes
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual
Note
The group object is not enabled.
The group object is enabled.
Position after reference movement
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 141