ABB i-bus® KNX PARAMETERS
7.10.3.1
Parameter setting
This parameter can be used to define whether the settings for the parameter window are adopted from
the template or each parameter is set individually.
Options
Apply from template
Individual
7.10.3.1.1
DEPENDENT PARAMETER
Switching status for safety priority x
This parameter can be used to define the relay switching position in case of safety priority.
More information → Safety priority, Page 80.
This parameter is visible only if, in the Parameter window Safety/Weather alarms, the following option
was set for the parameter Enable group object "Safety priority x": Yes .
In case of a safety priority, the output cannot be operated via other group objects, manual operation
or the i-bus® Tool until the safety priority is canceled.
Higher-priority safety functions will continue to run.
Options
No reaction/deactivated
ON
OFF
Unchanged (disable)
Options
No reaction/deactivated
ON
OFF
Unchanged (disable)
Condition for visibility:
Parameter window Safety \ Parameter Parameter setting \ Option Individual
The parameterization is adopted from the template for each parameter.
Parameters can be set individually.
Note
Note
The relay switching position remains unchanged. The output does not react to the safety priority.
The relay switching position is On.
The relay switching position is Off.
The relay switching position remains unchanged and is disabled in this position.
As long as disabling is active, the relay switching position cannot be changed via group objects, man-
ual operation or the i-bus® Tool.
Higher-priority safety functions will continue to run.
Switching status for safety priority x
Forced operation (1 bit / 2 bit)
Disable
Switching state on cancellation of disabling, forced operation and safety priority
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 198