ABB i-bus® KNX GROUP OBJECTS
No.
Function
121
Disable
This group object can be used to disable the output. The function Disable overrides the active signals of the output. The relay contact position can be
defined in the parameter Disable.
Telegram value:
1 = disable
0 = enable
Note
Disabling can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Safety \ Option Yes
Parameter window Switch Actuator A \ Parameter window Safety \ Parameter Parameter setting \ Option Individual \ Parameter Disable \ Option
ON \ OFF \ Unchanged (disable)
Forced operation, 1-bit
122
This group object can be used to activate 1-bit forced operation. The telegram value used to activate/deactivate forced operation can be defined in the
parameter Forced operation (1 bit / 2 bit).
When forced operation is activated, the relay switching contact will assume the state defined in the parameter Switching status during forced opera-
tion. The output cannot be controlled via KNX commands while forced operation is active. When forced operation is deactivated, the relay switching con-
tact will assume the state defined in the Switching state on cancellation of disabling, forced operation and safety priority parameter and operation will
be enabled.
Telegram value:
1 = forced operation active, state On/Off/Unchanged
0 = forced operation inactive
Note
Forced operation can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Safety \ Option Yes
Parameter window Switch Actuator A \ Parameter window Safety \ Parameter Parameter setting \ Option Individual \ Parameter Forced operation
(1 bit / 2 bit) \ Option Activated 1 bit – 0 active \ Option Activated 1 bit – 1 active
122
Forced operation, 2-bit
This group object can be used to activate 2-bit forced operation.
With 2-bit forced operation, the value of the group object determines the switching state. The first bit activates forced operation. The second bit
switches between the two states.
The output cannot be controlled via KNX commands while forced operation is active. When forced operation is deactivated, the relay switching contact
will assume the state defined in the Switching state on cancellation of disabling, forced operation and safety priority parameter and operation will be
enabled.
Telegram value (bit 1 | bit 0):
0 | 0 = forced operation inactive
0 | 1 = forced operation inactive
1 | 0 = forced operation active, state Off
1 | 1= forced operation active, state On
Note
Forced operation can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Safety \ Option Yes
Parameter window Switch Actuator A \ Parameter window Safety \ Parameter Parameter setting \ Option Individual \ Parameter Forced operation
(1 bit / 2 bit) \ Option Activated 2 bit
Disable staircase lighting
123
This group object can be used to disable the function Staircase lighting . If the function Staircase lighting is disabled, the switch-on command is for-
warded without time function in the function chain and the output reacts according to its parameterization.
Telegram value:
1 = function Staircase lighting disabled
0 = function Staircase lighting enabled
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Staircase lighting
Parameter window Switch Actuator A \ Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual \ Parameter Disable
staircase lighting via group object \ Option Yes
Group Object Name
Channel A: Switch
Channel A: Switch
Channel A: Switch
Channel A: Switch
Data Point Type Length
DPT 1.003
1 bit
DPT 1.003
1 bit
DPT 2.001
2 bit
DPT 1.003
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 234
Flags
C
W
C
W
C
W
C
W