ABB i-bus® KNX PARAMETERS
7.9.6.1.3
DEPENDENT PARAMETER
Enable group object "Disable direct operation"
This parameter can be used to define whether the group object Disable direct operation is enabled. This
group object can be used to disable changing to direct operation.
Options
No
Yes
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual
7.9.6.1.4
DEPENDENT PARAMETER
Position for sun = 1 (sun)
This parameter can be used to define how the blind/shutter reacts when the value 1 is received on group
object Sun .
Options
No reaction
Up
Down
Stop
Scene assignment
Individual position
Receive height and slat via
group objects
Receive only slat via group
object
Options
No reaction
Up
Down
Stop
Scene assignment
Individual position
Receive height and slat via
group objects
Receive only slat via group
object
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual
The group object is not enabled.
The group object is enabled.
If the blind/shutter is moving, it will continue until reaching the target position. If the blind/shutter is
at rest, its position will remain unchanged.
The blind/shutter moves to the upper end position
The blind/shutter moves to the lower end position
If the blind/shutter is moving, it will be stopped. If the blind/shutter is at rest, its position will remain
unchanged.
The scene assigned to the Shutter Actuator output pair is performed.
The required positions of the blind/shutter and slats (depending on operating mode) can be defined.
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
The required blind/shutter and slat positions are received via the group objects Sun: Move to height
and Sun: Move slat .
The required slat position is received via the group object Sun: Move slat .
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
The group object Sun: Move slat is available only in the Operating mode Blind/shutter control with
slat adjustment .
The group object Sun: Move slat is available only in the Operating mode Blind/shutter control with
slat adjustment .