ABB i-bus® KNX GROUP OBJECTS
No.
Function
120
Slat adjustment/stop Up-Down
The reaction on receipt of a telegram depends on the Operating mode:
Blind/shutter control without slat adjustment : If a telegram is received on this group object (irrespectively of the value 0 or 1), the moving blind/
shutter will be stopped.
Blind/shutter control with slat adjustment : If the blind/shutter is at rest, the slat position can be changed.
Telegram value:
1 = stop/close slats
0 = stop/open slats
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Operating
mode \ Option Blind/shutter control with slat adjustment
121
Enable limitation
Travel range limitation can be activated with this group object. If limitation is activated, the blind/shutter will move only in the travel range defined by
the Upper limit (0 % = top; 100 % = bottom) and Lower limit (0 % = top; 100 % = bottom) parameters.
Telegram value:
1 = limitation active
0 = limitation inactive
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Operating
mode \ Option Blind/shutter control with slat adjustment
Parameter window Shutter Actuator A+B \ Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual \ Parameter Limit
travel range via group object \ Option Enable limitation
Move blind/shutter Up-Down limited
121
If a telegram with the value 0 is received on this group object, the blind/shutter will be moved up to the parameterized limit. If a telegram with the value
1 is received, the blind/shutter will be moved down to the parameterized limit.
Telegram value:
1 = down limited
0 = up limited
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual \ Parameter Limit travel
range via group object \ Option Move blind/shutter Up-Down limited
Move to position height
122
This group object can be used to move the blind/shutter.
The slat position after the target position is reached corresponds to the slat position before the movement. If a telegram is received on the group object
Move to position slat during the movement, the slats will be set according to the received value after the target position has been reached.
Telegram value:
0 % = upper end position
1 ... 99 % = intermediate position
100 % = lower end position
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual \ Parameter Enable
group objects "Move to pos. height/Move to pos. slat" \ Option Yes
123
Move to position slat
This group object can be used to move the blind/shutter slats. The slats are positioned only after the movement is ended.
Telegram value:
0 % = slats open
1 ... 99 % = intermediate position
100 % = slats closed
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Operating
mode \ Option Blind/shutter control with slat adjustment
Parameter window Shutter Actuator A+B \ Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual \ Parameter Enable
group objects "Move to pos. height/Move to pos. slat" \ Option Yes
Group Object Name
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Data Point Type Length
DPT 1.007
1 bit
DPT 1.017
1 bit
DPT 1.008
1 bit
DPT 5.001
1 byte
DPT 5.001
1 byte
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 228
Flags
C
W
C
W
C
W
C
W
C
W

Advertisement