ABB i-bus® KNX PARAMETERS
7.9.7.1.3.1
DEPENDENT PARAMETER
Send value of group object
This parameter can be used to define whether the value of the group object will be sent to the
ABB i-bus® KNX.
Options
No, update only
After change
On request
After change or on request
Condition for visibility:
Parameter window Status messages \ Parameter Parameter setting \ Option Individual  \ Parameter En-
able group object "Status Operability" \ Option Yes
7.9.7.1.4
DEPENDENT PARAMETER
Enable group object "Status Automatic sun protection"
This parameter can be used to enable the group object Status Automatic sun protection . This group ob-
ject indicates whether automatic control of the output is activated or deactivated.
This group object can be used to have an LED on the button to indicate the status of automatic control
to the user.
Options
No
Yes
Condition for visibility:
Parameter window Status messages \ Parameter Parameter setting \ Option Individual
The value of the group object is updated but not sent.
The value of the group object is sent after every change.
The value of the group object is sent on request. A request can be triggered by sending the value 0 or
1 on the group object Request status values .
The value of the group object is sent after a change or on request. A request can be triggered by
sending the value 0 or 1 on the group object Request status values .
The group object is not enabled.
The group object is enabled.
Send value of group object