ABB i-bus® KNX GROUP OBJECTS
No.
Function
137
Status Operability
This group object can be used to output whether KNX operation of the output is enabled or disabled. KNX operation is disabled if
one of the safety functions is active
automatic sun protection is active
the device is in Manual operation mode
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after KNX operation is disabled/enabled.
Telegram value:
1 = operation enabled
0 = operation disabled
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group object "Status Operability" \ Option Yes
138
Status Automatic sun protection
This group object can be used to output whether automatic sun protection control is activated or deactivated.
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after activation/deactivation of the automatic function.
Telegram value:
1 = automatic sun protection activated
0 = automatic sun protection deactivated
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group object "Status Automatic sun protection" \ Option Yes
Status information
139
This group object can be used to output status information about the output's operating state.
The sending behavior can be defined in the Send value of group object parameter. If the "On request" or "After change or on request" option is selected,
the status is sent each time a bit value is changed.
Bit 0: Manual operation
Telegram value:
1 = active
0 = inactive
Bit 1: Disable
Telegram value:
1 = active
0 = inactive
Bit 2: Forced operation
Telegram value:
1 = active
0 = inactive
Bit 3: Frost alarm
Telegram value:
1 = active
0 = inactive
Bit 4: Rain alarm
Telegram value:
1 = active
0 = inactive
Bit 5: Wind alarm
Telegram value:
1 = active
0 = inactive
Bit 6: Automatic sun protection
Telegram value:
1 = active
0 = inactive
Bit 7: i-bus® Tool
Telegram value:
1 = active
0 = inactive
More information → Code table for 8-bit status byte (Shutter), Page 248.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group object "Status information" \ Option Yes
Group Object Name
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Data Point Type Length
DPT 1.011
1 bit
DPT 1.011
1 bit
nonDPT
1 byte
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 232
Flags
C R
T
C R
T
C R
T