ABB i-bus KNX Product Manual page 22

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PRODUCT OVERVIEW
3.4.3
Operating and display elements
A device with 24 channels (A ... X) is described below.
In Shutter mode, the function of the Output button/LEDs is identical for every shutter output pair.
Only the buttons/LEDs I and II are described below.
Button/LED
Programming
Tab.  7: Operating and display elements – general
Manual operation
Button/LED
S button / LED Manual operation
LED Group
Output button/ Output status LED
Tab.  8: Operating and display elements – manual operation
More information → Manual operation, Page 82.
Note
Note
Description/function
Assignment of the physical address
Description/function
Select relay group: Short button push < 2 s.
Switch to KNX operation:
Button push 2 ... 5 s
Selection of all relays (for central Off).
Long button push> 5 s.
Switch mode:
Switch outputs individually (toggle func-
tion)
Button I: First output of group
(A/E/I/M/Q/U)
Taste II: Second output of group
(B/F/J/N/R/V)
Button III: Third output of group
(C/G/K/O/S/W)
Button IV: Fourth output of group
(D/H/L/P/T/X)
Shutter mode:
Control shutter outputs
Button I:
Long button push > 1 s: Shutter Up
Short button push < 1 s: Shutter STOP/slat
adjustment
Taste II:
Long button push > 1 s: Shutter Down
Short button push < 1 s: Shutter STOP/slat
adjustment
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 22
LED indicator
LED On: Programming mode active
LED indicator
Manual operation active: LED: ON
KNX operation active: LED: OFF
Manual operation disabled:
LED: Flashing (1 Hz) or device is controlled
via i-bus® Tool
LED On: Group selected
LED Off: Group not selected
Switch mode:
LED On: Relay contact closed
LED Off: Relay contact open
LED flashing (1 Hz): Output disabled; manual
operation not possible.
Shutter mode:
LED I On and LED II Off: Upper end position
LED I Off and LED II On: Lower end position
LED I Off and LED II Off: Intermediate posi-
tion
LED I flashing (1 Hz) and LED II Off: Moving
up
LED I Off and LED II flashing (1 Hz): Moving
down
LED I flashing (1 Hz) and LED II flashing
(1 Hz): Output disabled
LED I flashing (5 Hz) and LED II flashing
(5 Hz): Signals the active shutter output (af-
ter the group is changed or after the operat-
ing mode is changed to Manual operation )

Advertisement

Table of Contents
loading

Table of Contents