ABB i-bus KNX Product Manual page 31

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PRODUCT OVERVIEW
3.5.4
Technical data
3.5.4.1
General technical data
Supply
Connections
Connection terminals
Degree of protection and protection
class
Isolation category
SELV
Temperature range
Ambient conditions
Design
Dimensions
Mounting
Approvals
3.5.4.2
Device type
Device type
Observe software information on the website → www.abb.com/knx.
The device supports the locking function of a KNX device in ETS. If a BCU code was assigned, the de-
vice can be read and programmed only with this BCU code.
Bus voltage
Current consumption, bus
Power loss, bus
Power loss, device
KNX
Screw terminal
Ferrule without plastic sleeve
Ferrule with plastic sleeve
TWIN ferrules
Ferrule contact pin length
Tightening torque
Degree of protection
Protection class
Overvoltage category
Pollution degree
Fire classification
KNX safety extra low voltage
Operation
Transport
Storage
Maximum air humidity
Modular installation device (MDRC)
Design
Housing/color
Dimensions
Mounting width in space units
Mounting depth
35 mm mounting rail
Mounting position
Weight (net)
KNX certification
CE marking
Switch/Shutter Actuator
Application
Maximum number of group objects
Maximum number of group addresses
Maximum number of assignments
Note
Note
21 ... 32 V DC
< 12 mA
Max. 250 mW
7.5 W
Ø 0.8 mm single core (via bus connection terminal)
Screw terminal with universal head (PZ 1)
0.2 ... 4 mm² stranded, 2 × (0.2 ... 2.5 mm²)
0.2 ... 6 mm² single core, 2 × (0.2 ... 4 mm²)
0.25 ... 2.5 mm²
0.25 ... 4 mm²
0.5 ... 2.5 mm²
Min. 10 mm
Max. 0.6 Nm
IP 20 to EN 60529
II to EN 61140
III to EN 60664-1
II to EN 60664-1
Flammability V-0 as per UL94
SELV 24 V DC
–5 ... +45 °C
–25 ... +70 °C
–25 ... +55 °C
95 %, no condensation allowed
Modular installation device
pro M
Plastic, gray
90 × 210 × 63.5 mm (H × W × D)
12 modules
63.5 mm
To EN 60715
Any
0.72 kg
To EN 50090-1, -2
In accordance with the EMC and Low Voltage Directives
SAH/S 24.6.7.1
Switch/Shutter 24f 16 A / ...
... = current version number of the application
610
1,000
1,000
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 31