ABB i-bus KNX Product Manual page 161

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.9.5.1.2
DEPENDENT PARAMETER
Position for rain alarm
This parameter can be used to define the blind/shutter reaction during a rain alarm.
In case of a weather alarm, the blind/shutter cannot be operated via other group objects, manual op-
eration or the i-bus® Tool until the weather alarm is canceled. Travel range limits are not taken into ac-
count with weather alarms.
Options
No reaction/deactivated
Up
Down
Stop
Unchanged (disable)
Scene assignment
Individual position
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual
7.9.5.1.2.1
DEPENDENT PARAMETER
Scene assignment
This parameter can be used to define which scene number is retrieved.
The scene assignment must be defined in Parameter window Scene assignments, in the parameter En-
able scene assignment x.
Options
1 ... 16
Condition for visibility:
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual  \ Parameter Posi-
tion for rain alarm \ Option Scene assignment
Note
If the blind/shutter is moving, it will continue until reaching the target position. If the blind/shutter is
at rest, its position will remain unchanged. The Shutter Actuator output pair does not react to the
alarm.
The blind/shutter moves to the upper end position
The blind/shutter moves to the lower end position
If the blind/shutter is moving, it will be stopped. If the blind/shutter is at rest, its position will remain
unchanged.
If the blind/shutter is moving, it will continue until reaching the target position. If the blind/shutter is
at rest, its position will remain unchanged. The blind/shutter is then disabled in this position.
The scene assigned to the Shutter Actuator output pair is performed.
The required positions of the blind/shutter and slats (depending on operating mode) can be defined.
Note
Scene assignment
Position height (0 % = top; 100 % = bottom)
Position slat (0 % = open; 100 % = closed)
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 161