ABB i-bus® KNX GROUP OBJECTS
No.
Function
14
End manual operation
This group object can be used to end Manual operation mode.
Telegram value:
1 = end manual operation
0 = end manual operation
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes
8.4
Group objects Safety
No.
Function
15 ... 17
Safety priority x
If the device receives a telegram with the value 1 on one of these group objects, the reaction set in the parameter Switching status for safety priority x
will take place in the assigned Switch Actuator outputs.
An active safety priority overrides operation of the device.
Order of priority → Priorities for Switch Actuator, Page 99.
If the device does not receive a telegram on one of these group objects within the interval set in the parameter Cyclical monitoring interval (0 = cycl.
monitoring deactivated), a fault will be assumed and the set reaction will take place. The first telegram after correction of the problem determines
whether the reaction during the problem is retained:
Value 1 = set reaction is retained
Value 0 = set reaction is canceled
The monitoring period is restarted after a telegram is received, after the device is programed and on bus voltage recovery.
Telegram value:
1 = alarm (normal operation disabled)
0 = no alarm
Condition for visibility:
Parameter window Safety/Weather alarms \ Parameter Enable group object "Safety priority x" \ Option Yes
18 ... 20
Wind alarm x
If the device receives a telegram with the value 1 on one of these group objects, the reaction set in the parameter Position on wind alarm will take place
in the assigned shutter outputs.
An active weather alarm overrides operation of the device.
Order of priority → Priorities for Shutter Actuator, Page 98.
If the device does not receive a telegram on one of these group objects within the interval set in the parameter Cyclical monitoring interval (0 = cycl.
monitoring deactivated), a fault will be assumed and the set reaction will take place. The first telegram after correction of the problem determines
whether the reaction during the problem is retained:
Value 1 = set reaction is retained
Value 0 = set reaction is canceled
The monitoring period is restarted after a telegram is received, after the device is programed and on bus voltage recovery.
Telegram value:
1 = alarm (normal operation disabled)
0 = no alarm
Condition for visibility:
Parameter window Safety/Weather alarms \ Parameter Enable group object "Wind alarm x" \ Option Yes
21
Rain alarm
If the device receives a telegram with the value 1 on this group object, the reaction set in the parameter Position for rain alarm will take place in the as-
signed shutter outputs.
An active weather alarm overrides operation of the device.
Order of priority → Priorities for Shutter Actuator, Page 98.
If the device does not receive a telegram on this group object within the interval set in the Cyclical monitoring interval (0 = cycl. monitoring deactivated)
parameter, a fault will be assumed and the set reaction will take place. The first telegram after correction of the problem determines whether the reac-
tion during the problem is retained:
Value 1 = set reaction is retained
Value 0 = set reaction is canceled
The monitoring period is restarted after a telegram is received, after the device is programed and on bus voltage recovery.
Telegram value:
1 = alarm (normal operation disabled)
0 = no alarm
Condition for visibility:
Parameter window Safety/Weather alarms \ Parameter Enable group object "Rain alarm" \ Option Yes
Group Object Name
Device: Manual operation
Group Object Name
Safety: Switch
Safety: Shutter
Safety: Shutter
Data Point Type Length
DPT 1.003
1 bit
Data Point Type Length
DPT 1.005
1 bit
DPT 1.005
1 bit
DPT 1.005
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 221
Flags
C
W
Flags
C
W T A
C
W T A
C
W T A