ABB i-bus® KNX GROUP OBJECTS
No.
Function
140
Scene 1 ... 64
This group object can be used to send a scene telegram. The scene telegram includes the scene number and information about whether the scene is re-
trieved or the relay switching state is saved in the scene.
Assignment to a scene number can be performed in the Parameter window Scene assignments, and this applies only to the output in which the scene
assignment was set.
Telegram value:
0 ... 63 = retrieve scene x (x = 1 ... 64)
128 ... 191 = save scene x (x = 1 ... 64)
More information → Code table 8-bit scene, Page 254.
Note
With the functions Weather alarm , Disable , Forced operation or Automatic sun protection , changing this group object does not necessarily result in a
changed blind/shutter position.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Scenes \ Option Yes
141 ... 144
Retrieve scene assignment x
This group object can be used to retrieve a scene assignment.
Telegram value:
1 = retrieve scene assignment x (x = 1 ... 4)
0 = retrieve scene assignment x (x = 1 ... 4)
Note
With the functions Weather alarm , Disable , Forced operation or Automatic sun protection , changing this group object does not necessarily result in a
changed blind/shutter position.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Scenes \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Scene assignments \ Parameter Parameter setting \ Option Individual \ Parameter
Enable scene assignment x \ Option Yes \ Parameter Scene retrieval additionally via group object \ Option Yes
8.30
Group objects Channel A: Switch
No.
Function
119
Switch
This group object can be used to switch the output On and Off.
NO contact telegram value:
1 = On
0 = Off
NC contact telegram value:
1 = Off
0 = On
Note
With the Logic/Threshold , Disable and Forced operation functions or the safety priority , changing this group object does not necessarily result in a
changed contact position.
Each relay can perform only a limited number of switching operations per minute. Frequent switching can cause a switching delay. More information →
Technical data.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator
120
Status Switch
This group object can be used to indicate the relay contact position. The telegram value is defined in the parameter Value of group object "Status
switch".
Telegram value:
1 = contact closed or open, depending on parameterization
0 = contact open or closed, depending on parameterization
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator
Parameter window Switch Actuator A \ Parameter window Basic settings \ Parameter Parameter setting \ Option Individual \ Parameter Feedback
of switching state via group object "Status switch" \ Option Yes
Group Object Name
Channel A: Shutter
Channel A: Shutter
Group Object Name
Channel A: Switch
Channel A: Switch
Data Point Type Length
DPT 18.001
1 byte
DPT 1.017
1 bit
Data Point Type Length
DPT 1.001
1 bit
DPT 1.011
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 233
Flags
C
W
C
W
Flags
C
W
C R
T