ABB i-bus® KNX GROUP OBJECTS
No.
Function
123
Disable delay for switching ON and OFF
This group object can be used to disable the function Delay for switching ON and OFF . If the function Delay for switching ON and OFF is disabled, the
switch-on command is forwarded without time function in the function chain and the output reacts according to its parameterization.
Telegram value:
1 = delay for switching ON and OFF disabled
0 = delay for switching ON and OFF enabled
Note
If a delay time was set for a scene assignment in the parameter Delay, this group object can also be used to disable the delay of the scene.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Delay for switching ON and OFF
Parameter window Switch Actuator A \ Parameter window Delay for switching ON and OFF \ Parameter Parameter setting \ Option Individual \ Pa-
rameter Disable delay for switching ON and OFF via group object \ Option Yes
124
Staircase lighting permanent ON
This group object can be used to switch on the output permanently when the function Staircase lighting is active. Other functions continue to run in the
background, but they do not trigger any switching operation.
Telegram value:
1 = starts Permanent ON operation
0 = ends Permanent ON operation
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Staircase lighting
Staircase lighting time
125
This group object can be used to set the Staircase lighting time.
Telegram value:
0 ... 65,535 s
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Staircase lighting
Parameter window Switch Actuator A \ Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual \ Parameter
Change staircase lighting time via group object \ Option Yes
126
Warning staircase lighting
This group object can be used to indicate the end of the Staircase lighting time. The group object is set to the value 1 at the beginning of the Warning
time. The group object is set to the value 0 when the Warning time elapses. The group object can be used to switch a warning light.
Telegram value:
1 = warning time running
0 = warning time not running
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Switch Actuator A \ Parameter window Functions \ Parameter Application \ Option Switch Actuator \ Parameter Enable function
Time \ Option Staircase lighting
Parameter window Switch Actuator A \ Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual \ Parameter Warn-
ing before switching off the staircase lighting \ Option Via group object \ Via object and quick switching ON/OFF
Group Object Name
Channel A: Switch
Channel A: Switch
Channel A: Switch
Channel A: Switch
Data Point Type Length
DPT 1.003
1 bit
DPT 1.001
1 bit
DPT 7.005
2 bytes
DPT 1.001
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 235