ABB i-bus KNX Product Manual page 231

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX GROUP OBJECTS
No.
Function
132
Disable direct operation
This group object can be used to disable direct operation. If direct operation is disabled, incoming telegrams on the direct group objects will not be exe-
cuted.
Automatic control has a higher priority. Even if direct operation is enabled, direct telegrams are executed only when automatic control is disabled.
Telegram value:
1 = direct operation disabled
0 = direct operation enabled
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual \ Param-
eter Enable group object "Disable direct operation" \ Option Yes
Status Height
133
This group object can be used to output the current position of the blind/shutter.
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after a movement is completed.
Telegram value:
0 % = upper end position
1 % ... 99 % = intermediate position
100 % = lower end position
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group objects "Status Height/Slat" \ Option Yes
134
Status Slat
This group object can be used to output the current position of the slats.
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after a movement is completed.
Telegram value:
0 % = slats open
1 % ... 99 % = intermediate position
100 % = slats closed
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group objects "Status Height/Slat" \ Option Yes
135
Status Upper end position
This group object can be used to output whether the blind/shutter is at the upper end position.
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after the upper end position is reached or left.
Telegram value:
1 = blind/shutter in upper end position
0 = blind/shutter not in upper end position
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group objects "Status Upper/Lower end pos." \ Option Yes
136
Status Lower end position
This group object can be used to output whether the blind/shutter is at the lower end position.
The sending behavior can be defined in the parameter Send value of group object. If the "On request" or "After change or on request" option is selected,
the status is sent after the lower end position is reached or left.
Telegram value:
1 = blind/shutter in lower end position
0 = blind/shutter not in lower end position
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Status messages \ Parameter Parameter setting \ Option Individual \ Parameter En-
able group objects "Status Upper/Lower end pos." \ Option Yes
Group Object Name
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Data Point Type Length
DPT 1.003
1 bit
DPT 5.001
1 byte
DPT 5.001
1 byte
DPT 1.011
1 bit
DPT 1.011
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 231
Flags
C
W
C R
T
C R
T
C R
T
C R
T

Advertisement

Table of Contents
loading

Table of Contents