ABB i-bus KNX Product Manual page 74

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PRODUCT OVERVIEW
3.11.4.3
Output, rated current 16 A
Rated values
Switching currents
Service life
Switching times
The switching times apply only after the bus voltage has been applied to the device for at least 30 sec-
onds. The typical relay delay is approx. 20 ms.
3.11.4.4
Output, lamp load 16 A
Lamps
Fluorescent lamps
Low-voltage halogen lamps
Dulux lamp
Mercury-vapor lamp
Switching capacity (switching contact) Maximum peak inrush current I
Number of ballasts (T5/T8, single ele-
ment)
Energy-saving lamps
Rated motor power
The device features independent switching relays that are linked by software to control the shutters.
The contacts are not mutually electromechanically interlocked.
The peak inrush current I
peak inrush current I
Switch Actuator output for the various ballast types. The number of ballasts specified in the table can
be only a sample guide value.
Number of outputs
U
Rated voltage
n
I
Rated current
n
Maximum current per device
AC3 operation (cos φ= 0.45) to EN 60947-4-1
AC1 operation (cos φ= 0.8) to EN 60947-4-1
Fluorescent lighting load according to EN 60669-1
minimum switching current at 12 V AC
minimum switching current at 24 V AC
DC switching capacity, resistive load, at 24 V DC
Mechanical service life
Electrical endurance of switching contacts according to
IEC 60 947-4-1:
AC1 (240 V/cos φ=0.8)
AC3 (240 V/cos φ=0.45)
AC5a (240 V/cos φ=0.45)
Maximum output relay position changes per minute if all
relays are switched.
Maximum output relay position changes per minute if
only one relay is switched.
Note
Incandescent lamp load
Uncompensated
Parallel compensated
DUO circuit
Inductive transformer
Electronic transformer
Halogen 230 V
Uncompensated
Parallel compensated
Uncompensated
Parallel compensated
Maximum peak inrush current I
Maximum peak inrush current I
18 W (ABB ballast 1 x 18 SF)
24 W (ABB ballast T5 1 x 24 CY)
36 W (ABB ballast 1 x 36 CF)
58 W (ABB ballast 1 x 58 CF)
80 W (Helvar EL 1 x 80 SC)
LED lamps
Note
Note
is the typical ballast load current that results during switching. Using the
p
, it is possible to calculate the maximum number of switchable ballasts at the
p
24 switch / 12 shutter
230 V AC (50/60 Hz)
16 A
200 A
6 A / 230 V AC
16 A / 230 V AC
10 mA
10 mA
6 A
> 10⁶ cycles
> 10⁵ cycles
> 6 × 10³ cycles
5
120
1,200 W
800 W
800 W
1,000 W
1,000 W
1,000 W
800 W
(150 ms)
200 A
p
(250 ms)
160 A
p
(600 ms)
100 A
p
10
10
7
5
3
250 W
1,380 W
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 74