ABB i-bus® KNX PARAMETERS
7.9.6.1.6.2
DEPENDENT PARAMETER
Position slat (0 % = open; 100 % = closed)
This parameter can be used to define the position to which the blind/shutter slats are moved.
The position will be approached only with deactivated automatic sun protection.
This parameter is available only in Operating mode Blind/shutter control with slat adjustment .
Options
0 ... 100 %
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual  \ Pa-
rameter Position for sun = 0 (no sun) \ Option Individual position
7.9.6.1.7
DEPENDENT PARAMETER
Delay for sun = 0
This parameter can be used to set the delay time after which the blind/shutter moves into position
when the sun does not shine. This can serve to avoid unnecessary position changes due to brief periods
of cloud shadowing.
Options
00:00:00 ... 01:40:00 hh:mm:ss
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual
7.9.6.1.8
DEPENDENT PARAMETER
Read activated automatic sun protection group objects after bus voltage recovery and download
This parameter can be used to define whether the active automatic group objects are read after bus
voltage recovery.
The read flags must be set for the corresponding group objects of the sending device.
Options
No
Yes
Condition for visibility:
Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual
Note
Note
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 177