ABB i-bus® KNX GROUP OBJECTS
No.
Function
127
Activation of automatic sun protection
This group object can be used to activate the function Automatic sun protection . Automatic sun protection can be controlled via the following group ob-
jects:
Sun
Sun: Move to height
Sun: Move slat
When automatic sun protection is active, the output updates itself based on the values stored in the automatic sun protection group objects.
When automatic sun protection is deactivated, the output does not react to incoming telegrams on the automatic sun protection group objects. Move-
ments initiated by automatic commands are completed when automatic sun protection is ended.
Telegram value:
1 = automatic sun protection activated, direct operation deactivated
0 = automatic sun protection deactivated, direct operation activated
Note
A reference movement interrupts automatic sun protection. Incoming automatic telegrams are executed after the reference movement is completed.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
Sun
128
If a telegram with the value 1 is received on this group object, the blind/shutter will move to the position defined in the parameter Position for sun = 1
(sun). If a telegram with the value 0 is received, the blind/shutter will move to the position defined in the parameter Position for sun = 0 (no sun).
To prevent frequent alternation between moving up and moving down due to weather, the reaction to incoming telegrams can be delayed via the pa-
rameters Delay for sun = 1 and Delay for sun = 0.
Telegram value:
1 = sun
0 = no sun
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
129
Sun: Move to height
If automatic sun protection is active and a telegram is received on this group object, the blind/shutter will be positioned according to the value received.
If automatic sun protection is deactivated, telegrams on this group object are ignored.
When the the target position is reached, the slats are set to the same position as before the movement. If a telegram is received on the group object
Sun: Move slat during the movement, the slats will be set according to the received value after the target position is reached.
Telegram value:
0 % = upper end position
1 % ... 99 % = intermediate position
100 % = lower end position
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
Sun: Move slat
130
If automatic sun protection is active and a telegram is received on this group object, the slats will be positioned according to the value received. If auto-
matic sun protection is deactivated, telegrams on this group object are ignored.
Telegram value:
0 % = slats open
1 % ... 99 % = intermediate position
100 % = slats closed
Note
The slats are positioned only after the blind/shutter reaches the target position.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
131
Disable automatic sun protection
This group object can be used to disable the function Automatic sun protection . If automatic sun protection is disabled, activation via the group object
Activation of automatic sun protection will not be possible and the output can be activated only via direct group objects.
Telegram value:
1 = automatic sun protection disabled
0 = automatic sun protection enabled
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Automatic sun protection \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Automatic sun protection \ Parameter Parameter setting \ Option Individual \ Param-
eter Enable group object "Disable automatic sun protection" \ Option
Group Object Name
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Data Point Type Length
DPT 1.003
1 bit
DPT 1.002
1 bit
DPT 5.001
1 byte
DPT 5.001
1 byte
DPT 1.003
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 230
Flags
C
W T A
C
W T A
C
W T A
C
W T A
C
W T A