ABB i-bus KNX Product Manual page 204

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.10.4.1.4
DEPENDENT PARAMETER
Warning before switching off the staircase lighting
This parameter can be used to define whether the user will be warned before the lighting is switched off.
Options
No
Via group object
Via quick switching OFF/ON
Via object and quick switching
ON/OFF
Condition for visibility:
Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual
7.10.4.1.4.1
DEPENDENT PARAMETER
Warning time
This parameter can be used to set the duration of the warning time. The warning time is added to the
Staircase lighting time.
Options
00:00:10 ... 00:00:45 ... 18:12:15 hh:mm:ss
Condition for visibility:
Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual  \ Parameter
Warning before switching off the staircase lighting \ Option Via group object
7.10.4.1.4.2
DEPENDENT PARAMETER
Quantity of Off/On changes
This parameter can be used to define the number of Off/On changes during the Warning time.
Options
1 ... 2 ... 5
Condition for visibility:
Parameter window Staircase lighting \ Parameter Parameter setting \ Option Individual  \ Parameter
Warning before switching off the staircase lighting \ Option Via quick switching OFF/ON
The user is not warned before the lighting is switched off.
The group object Warning staircase lighting is enabled. The group object is set to the value 1 at the
beginning of the Warning time. The group object is set to the value 0 when the warning time elapses.
The group object can be used to switch a warning light.
Warning time
The lighting is briefly switched off and then back on during the Warning time. The number of Off/On
changes can be set in the parameter Quantity of Off/On changes. The first Off/On change takes
place at the beginning of the warning time. Additional Off/On changes are uniformly distributed over
the remaining warning time.
Quantity of Off/On changes
Warning time
The user is warned before the lighting is switched off:
Via group object
Via quick switching OFF/ON
Quantity of Off/On changes
Warning time
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 204