ABB i-bus KNX Product Manual page 119

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.6.1.1
DEPENDENT PARAMETER
Group object "Connection A" after bus voltage recovery
This parameter can be used to define the value that will be written to the group object Connection A af-
ter bus voltage recovery.
Options
1
0
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option AND
7.6.1.2
DEPENDENT PARAMETER
Group object "Connection B" after bus voltage recovery
This parameter can be used to define the value that will be written to the group object Connection B af-
ter bus voltage recovery.
Options
1
0
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option AND
7.6.1.3
DEPENDENT PARAMETER
Invert result
This parameter can be used to define whether the result of the function Logic will be output inverted.
Options
No
Yes
Condition for visibility:
Parameter window Logic/Threshold 1 \ Parameter Function of the logic gate \ Option AND
The value 1 is written to the group object, but does not pass through the function Logic . Writing the
group object does not affect the result of the function Logic .
The value 0 is written to the group object, but does not pass through the function Logic . Writing the
group object does not affect the result of the function Logic .
The value 1 is written to the group object, but does not pass through the function Logic . Writing the
group object does not affect the result of the function Logic .
The value 0 is written to the group object, but does not pass through the function Logic . Writing the
group object does not affect the result of the function Logic .
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 119