ABB i-bus® KNX PARAMETERS
Example:
The slats are fully closed (= 100 %). The Slat adjustment Up telegram is received. The motor shaft
starts turning. However, the slats stay closed and adjustment begins only after the dead time expires.
Options
0 ... 5,000 ms
Condition for visibility:
Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual  \ Parameter Set
dead times \ Option Custom
7.9.4.1.9.3
DEPENDENT PARAMETER
Slippage of slat on change of direction
This parameter can be used to set the time required to compensate for the slat play after a change of di-
rection.
Example:
The slats are open (position 50 %). The Slat adjustment Down telegram is received. The slats close to
60 %.
A Slat adjustment Up telegram (=direction change) is received next. Owing to the slat play during a
change of direction, the slats will open only to 55% instead of returning to the slat open position (=
50%).
In order to position the slats exactly, the slat play during a change of direction must be compensated.
This parameter is available only in Operating mode Blind/shutter control with slat adjustment .
Options
0 ... 5,000 ms
Condition for visibility:
Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual  \ Parameter Set
dead times \ Option Custom
7.9.4.1.9.4
DEPENDENT PARAMETER
Slippage of blind/shutter on change of direction
This parameter can be used to set the time required to compensate for the blind/shutter play after a
change of direction.
Note
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 155