ABB i-bus® KNX PARAMETERS
7.10.5
Parameter window Delay for switching ON and OFF
This parameter window is visible only if, in the Parameter window Functions, the following option is
set for the parameter Enable function Time: Delay for switching ON and OFF .
The Parameter window Delay for switching ON and OFF can be used to set the reaction of the function
Delay for switching ON and OFF .
More information → Function Delay for switching ON and OFF, Page 94.
If several Shutter Actuator outputs are to be set to the same values, parameterization can be per-
formed in Parameter window Switch Actuator template.
Fig.  51: Parameter window Delay for switching ON and OFF
Parameter
• Parameter setting
• Delay for switching ON
• Delay for switching OFF
• Disable delay for switching ON and OFF via group object
7.10.5.1
Parameter setting
This parameter can be used to define whether the settings for the parameter window are adopted from
the template or each parameter is set individually.
Options
Apply from template
Individual
Note
Note
• Disable delay for switching ON and OFF after bus voltage recovery
The parameterization is adopted from the template for each parameter.
Parameters can be set individually.
Delay for switching ON
Delay for switching OFF
Disable delay for switching ON and OFF via group object
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 207