ABB i-bus KNX Product Manual page 142

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX PARAMETERS
7.9.3.1.4.1
DEPENDENT PARAMETER
Position after reference movement
This parameter can be used to define the blind/shutter position after a reference movement.
Options
No reaction; remain in reference
position
Move to position before
reference movement
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual  \ Parameter Enable group
object "Trigger reference movement" \ Option Yes
7.9.3.1.5
DEPENDENT PARAMETER
Reversing time
This parameter can be used to define the duration of the reversing time.
The reversing time is the required pause while the blind/shutter changes direction. The device must be
deenergized during this period.
NOTICE
Setting a reversing time that is too short can damage the connected drive.
A reversing tim of 1 second is always used on bus voltage failure. The parameterized value applies dur-
ing operation with appplied bus voltage.
Options
50 ... 500 ... 5,000 ms
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual
The blind/shutter remains in the upper end position or lower end position as the reference position.
The blind/shutter is moved to the position it was in before the reference movement.
Pay attention to technical data for the connected drive
Note
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 142

Advertisement

Table of Contents
loading

Table of Contents