ABB i-bus® KNX PARAMETERS
7.9.3.1
Parameter setting
This parameter can be used to define whether the settings for the parameter window are adopted from
the template or each parameter is set individually.
Options
Apply from template
Individual
7.9.3.1.1
DEPENDENT PARAMETER
Travel time up
This parameter can be used to define how long the blind/shutter takes to move from the lower to the
upper end positions. The travel time must first be measured manually.
Physical and weather-related circumstances (frost, UV radiation, long-term use or use of heavy blind/
shutter types) mean that differing total travel times may result for a complete movement from the
lower end position to the upper end position (up) and from the upper end position to the lower end
position (down). The total travel times can be set separately to permit exact positioning of the blind/
shutter.
Options
00:01:00 ... 00:10:00 hh:mm:ss
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual
7.9.3.1.2
DEPENDENT PARAMETER
Travel time down
This parameter can be used to define how long the blind/shutter takes to move from the upper to the
lower end positions. The travel time must first be measured manually.
Physical and weather-related circumstances (frost, UV radiation, long-term use or use of heavy blind/
shutter types) mean that differing total travel times may result for a complete movement from the
lower end position to the upper end position (up) and from the upper end position to the lower end
position (down). The total travel times can be set separately to permit exact positioning of the blind/
shutter.
Options
00:01:00 ... 00:10:00 hh:mm:ss
Condition for visibility:
Parameter window Drive \ Parameter Parameter setting \ Option Individual
The parameterization is adopted from the template for each parameter.
Parameters can be set individually.
Note
Note
Travel time up
Travel time down
Disconnect output from power after
Enable group object "Trigger reference movement"
Reversing time
Delay time for drive