ABB i-bus KNX Product Manual page 220

Switch/shutter actuator
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus® KNX GROUP OBJECTS
No.
Function
6
Move to position height
This group object can be used to activate several shutter outputs of the device under central control and to move the blinds/shutters to a defined posi-
tion.
In the Parameter window Basic settings, in the Output reacts to central shutter group objects parameter, it can be individually defined whether the out-
put reacts to this group object.
The slat position after the target position is reached corresponds to the slat position before the movement. If a telegram is received on the group object
Move to position slat during the movement, the slats will be set according to the received value after the target position has been reached.
Telegram value:
0 % = upper end position
1 ... 99 % = intermediate position
100 % = lower end position
Note
With the functions Weather alarms , Disable , Forced operation or Automatic sun protection , changing this group object does not necessarily result in a
changed blind/shutter position.
Each relay can perform only a limited number of switching operations per minute. Frequent switching can cause a switching delay. More information →
Technical data.
Condition for visibility:
Parameter window Device settings \ Parameter Enable central Shutter group objects \ Option
Move to position slat
7
This group object can be used to activate several shutter outputs of the device under central control and to move the slats to a defined position. The
slats are positioned only after the movement is ended.
In the Parameter window Basic settings, in the Output reacts to central shutter group objects parameter, it can be individually defined whether the out-
put reacts to this group object.
Telegram value:
0 % = fully open
1 ... 99 % = intermediate position
100 % = fully closed
Note
With the functions Weather alarms , Disable , Forced operation or Automatic sun protection , changing this group object does not necessarily result in a
changed blind/shutter position.
Each relay can perform only a limited number of switching operations per minute. Frequent switching can cause a switching delay. More information →
Technical data.
Condition for visibility:
Parameter window Device settings \ Parameter Enable central Shutter group objects \ Option
8
Scene 1 ... 64
This group object can be used to send a scene telegram. The scene telegram includes the scene number and information about whether the scene is re-
trieved or the relay switching state is saved in the scene.
The assignment to a scene number can be made in the Parameter window Scene assignments (Shutter Actuator) or Parameter window Scene assign-
ment (Switch Actuator). All outputs assigned to this scene number perform the set reaction.
Telegram value:
0 ... 63 = retrieve scene x (x = 1 ... 64)
128 ... 191 = save scene x (x = 1 ... 64)
More information → Code table 8-bit scene, Page 254.
Note
With the priorities of the safety functions, a change in the value of this group object does not necessarily result in a changed contact position or blind/
shutter position.
Condition for visibility:
Parameter window Device settings \ Parameter Enable central Scene group object \ Option
8.3
Group objects Device
No.
Function
Status Manual operation
12
This group object indicates whether Manual operation mode is active.
Telegram value:
1 = manual operation active
0 = manual operation not active
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes
13
Enable/disable manual operation
This group object can be used to disable Manual operation mode.
If the device is in Manual operation mode, it will be ended and disabled when the value 0 is received.
Telegram value:
1 = enable manual operation
0 = disable manual operation
Condition for visibility:
Parameter window Manual operation \ Parameter Enable manual operation \ Option Yes
Group Object Name
Central: Shutter
Central: Shutter
Central: Scene
Group Object Name
Device: Manual operation
Device: Manual operation
Data Point Type Length
DPT 5.001
1 byte
DPT 5.001
1 byte
DPT 18.001
1 byte
Data Point Type Length
DPT 1.011
1 bit
DPT 1.003
1 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 220
Flags
C
W
C
W
C
W
Flags
C R
T
C
W