ABB i-bus® KNX GROUP OBJECTS
No.
Function
124
Trigger reference movement
This group object can be used to initiate a reference movement.
More information → Reference movement, Page 87.
Telegram value:
1 = reference movement lower end position
0 = reference movement upper end position
Note
A reference movement cannot be performed while a safety function is active.
The following actions will interrupt an active reference movement:
Receipt of a safety telegram
Activation of manual operation
A reference movement can be performed even if direct operation is disabled (via group object Disable direct operation ).
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator
Parameter window Shutter Actuator A+B \ Parameter window Blind/Shutter \ Parameter Parameter setting \ Option Individual \ Parameter Enable
group objects "Move to pos. height/Move to pos. slat" \ Option Yes
125
Disable
This group object can be used to disable the output for operation via direct commands and automatic commands.
If a telegram with the value 1 is received, the blind/shutter will be moved to the position defined in the parameter Position on disabling and disabled in
this position. If a telegram with the value 0 is received, the blind/shutter will be moved to the position defined in the parameter Position on cancellation
of weather alarm, disabling and forced operation.
Telegram value:
1 = disable
0 = enable
Note
Disabling can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Safety/Weather alarms \ Option Yes
Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual \ Parameter Position on disabling \ Option Up \ Down \
Stop \ Unchanged (disable) \ Scene assignment \ Individual position
126
Forced operation, 1-bit
This group object can be used to activate 1-bit forced operation. The telegram value used to activate/deactivate forced operation can be defined in the
parameter Forced operation (1 bit / 2 bit).
When forced operation is activated, the blind/shutter will be moved to the position defined in the parameter Position height (0 % = top; 100 % = bot-
tom). The output cannot be controlled via KNX commands while forced operation is active. When forced operation is deactivated, the blind/shutter will
be moved to the position defined in the parameter Position on cancellation of weather alarm, disabling and forced operation and operation will be en-
abled.
Telegram value:
1/0 = forced operation active
0/1 = forced operation inactive
Note
Forced operation can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Safety/Weather alarms \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual \ Parameter
Forced operation (1 bit / 2 bit) \ Option Activated 1 bit – 0 active \ Activated 1 bit – 1 active
Forced operation, 2-bit
126
This group object can be used to activate 2-bit forced operation.
With 2-bit forced operation, the value of the group object determines the switching state. The first bit activates forced operation. The second bit
switches between the two states.
The output cannot be controlled via KNX commands while forced operation is active. When forced operation is deactivated, the blind/shutter will be
moved to the position defined in the parameter Position on cancellation of weather alarm, disabling and forced operation and operation will be enabled.
Telegram value (bit 1 | bit 0):
0 | 0 = forced operation inactive
0 | 1 = forced operation inactive
1 | 0 = forced operation active, Off state
1 | 1 = forced operation active, On state
Note
Forced operation can be influenced via the i-bus® Tool.
Condition for visibility:
Parameter window Configuration \ Parameter Enable output X + Y \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Functions \ Parameter Application \ Option Shutter Actuator \ Parameter Enable
function Safety/Weather alarms \ Option Yes
Parameter window Shutter Actuator A+B \ Parameter window Safety/Weather \ Parameter Parameter setting \ Option Individual \ Parameter
Forced operation (1 bit / 2 bit) \ Option Activated 2 bit
Group Object Name
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Channel A: Shutter
Data Point Type Length
DPT 1.008
1 bit
DPT 1.003
1 bit
DPT 1.003
1 bit
DPT 2.001
2 bit
Product manual | SAH/S x.x.7.1 | 2CDC505173D0211 Rev. A 229
Flags
C
W
C
W
C
W
C
W