10.Select the "Topology" tab to assign the "partner port" to X150 P1 and click "OK" to confirm.
Note for the selection of the cable length that a longer cable length also increases the signal
runtime.
11.Select interface X150 in the SINUMERIK NCU and from the shortcut menu "PROFINET IO
Domain Management...".
12.In the list under "Station/device name", select the SINUMERIK NCU and with a double-click,
open the synchronization dialog in order to define the NCU as "Sync master".
CNC Commissioning: NC, PLC, Drive
Commissioning Manual, 12/2019, A5E48312804B AA
5.3 Extending the SIMATIC S7 project (PROFINET)
PLC commissioning
77