PLC commissioning
5.8 Configuring a network (NetPro) for PG/PC
4. Select the subnet "Ethernet(1)" and enter the following IP address and subnet mask for the
PG/PC:
– IP address 192.168.215.2
– Subnet mask 255.255.255.224
5. Deactivate the option "Set MAC address/Use ISO protocol" and confirm with "OK".
6. You can configure additional interfaces via "New".
All configured interfaces can then be viewed under the "Interface" tab:
The configured interfaces must be assigned in a device-specific manner to the available
hardware interfaces on the PG/PC. The sequence steps are laid out in the following section.
98
CNC Commissioning: NC, PLC, Drive
Commissioning Manual, 12/2019, A5E48312804B AA