PLC commissioning
5.3 Extending the SIMATIC S7 project (PROFINET)
5.3.3
Commissioning the PLC
Basic procedure
Perform the following steps:
● Insert the SINAMICS Control Unit in HW Config.
● Set the sync master and sync slaves.
● Configure the PROFINET interface.
● Configure the isochronous alarms.
● Save the configuration, compile and then download to the PLC.
● Establish the online connection to the target system and assign a device name to the
SINAMICS Control Unit.
Configuring a PROFINET connection
Procedure:
1. At the SINUMERIK NCU, select X150 and insert a PROFINET line via the "Insert" →
"PROFINET IO system" menu. Click the "New" button to insert a new subnet "Ethernet(1)":
2. Navigate in the catalog to "PROFINET IO" → "Drives" → "SINAMICS" → "SINAMICS S120"
→ "SINAMICS S120 CU320-2 PN".
74