Bus%1.Slave%2: %3: Check/acknowledge topology!

Parameters:
%1 = Bus number
%2 = Slave address
%3 = Name of the affected drive unit
Definitions:
The drive unit with the bus number and slave address specified in the alarm has detected an illegal difference between
reference topology and actual topology during the ramp-up when checking the DRIVE-CLiQ topology.
For this reason, the drive unit has stopped the ramp-up in the 'Topology error' state.
Reaction:
Alarm display.
Remedy:
- Check actual topology and possibly replug in line with the actual topology.
- Check DRIVE-CLiQ cables for breakage and problems with contacts.
- Test DRIVE-CLiQ components for operational functioning.
Note:
Under 'Setup > Drive system > Drive devices > Topology', HMI offers a suitable diagnostics (e.g. reference/actual
value comparison).
Program
Internal
Continuation:
120404
Setting up acyclic link %1 failed.%nSwitch off/on control, drives and HMI.
Parameters:
%1 = Name of connection
Definitions:
Setting up an acyclic link with a drive unit for file transfer from/to this drive unit has failed.
The file could not be transferred from/to this drive unit.
The affected drive unit has the bus number and slave address specified in the link name: /DRIVE_<Bus num-
ber>_<Slave address>.
Reaction:
Alarm display.
Remedy:
Execute the following measures in the sequence specified until the process leading to the alarm can be repeated suc-
cessfully:
1. Switch off/on control, drives and HMI, and then repeat the process leading to the alarm.
2. Load PROFIBUS configuration (HW Config) with same PLC and CP-Subnet-ID in PLC and CP, switch off/on control
and HMI, and then repeat the process leading to the alarm.
3. Return to factory settings of the affected drive unit, switch off/on control, drives and HMI, and then repeat the pro-
cess leading to the alarm.
4. Contact Siemens AG, Industry Sector, I DT MC, Hotline (Phone/Fax: see Alarm 1000) regarding the error text.
Program
Internal
Continuation:
120405
SINAMICS: Firmware update for DRIVE-CLiQ components is running.%nPlease wait for
the firmware update to be completed!
Definitions:
The firmware update is being executed for at least one DRIVE-CLiQ component.
Reaction:
Alarm display.
Remedy:
None required.
Please wait for the firmware update to be completed.
Completion of the firmware update is signaled by alarm 120406.
Program
Internal
Continuation:
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
HMI alarms
503