Power Unit: Dc Link Voltage, Undervoltage - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
Remedy:
- increase the ramp-down time
- activate the DC link voltage controller
- use a brake resistor or Active Line Module
- increase the current limit of the infeed or use a larger module (for the Active Line Module)
- check the device supply voltage
- check and correct the phase assignment at the VSM and at the power unit
- check the line supply phases.
See also: p0210 (Drive unit line supply voltage), p1240 (Vdc controller or Vdc monitoring configuration)
230003
<location>Power unit: DC link voltage, undervoltage
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an undervoltage condition in the DC link.
- line supply failure
- line supply voltage below the permissible value.
- line supply infeed failed or interrupted.
- line phase interrupted.
Note:
The monitoring threshold for the DC link undervoltage is the minimum of the following values:
- for a calculation, refer to p0210.
Remedy:
- check the line supply voltage
- check the line supply infeed and observe the fault messages relating to it (if there are any)
- check the line supply phases.
Note:
The ready signal for the infeed (r0863) must be connected to the associated drive inputs (p0864).
See also: p0210 (Drive unit line supply voltage)
230004
<location>Power unit: Overtemperature heat sink AC inverter
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The temperature of the power unit heat sink has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
- pulse frequency too high.
Fault value (r0949):
Temperature [1 bit = 0.01 °C].
Remedy:
- check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
- check the motor load.
- reduce the pulse frequency if this is higher than the rated pulse frequency.
Notice:
This fault can only be acknowledged after this alarm threshold for alarm A05000 has been undershot.
690
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0