SINAMICS alarms
Re message value = 1001:
- carry out a POWER ON (power off/on) for all components.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
Re message value = 1005:
- check the conditions for pulse enable.
Re message value = 1011:
- for diagnostics, refer to parameter (r9571).
Re message value = 1012:
- upgrade the Sensor Module software.
- check the encoder parameters in the encoder systems for equality (p9515/p9315, p9519/p9319, p9523/p9323,
p9524/p9324, p9525/p9325, p9529/p9329).
Re message value = 1020, 1021:
- check the communication link.
- increase the monitoring cycle clock settings (p9500, p9511).
- carry out a POWER ON (power off/on) for all components.
- replace the hardware.
Re message value = 1041:
- reduce the minimum current (p9588).
Re message value = 1042:
- increase the ramp-function generator ramp-up/down time (p1120/p1121).
- check that the current/speed control is set correctly (torque-generating/field-generating current and actual speed
value may not fluctuate).
- reduce the dynamic response of the setpoint value.
- increase the minimum current (p9588).
Re message value = 1043:
- increase the voltage tolerance (p9588).
- increase the ramp-function generator ramp-up/down time (p1120/p1121).
- check that the current/speed control is set correctly (torque-generating/field-generating current and actual speed
value may not fluctuate).
- reduce the dynamic response of the setpoint value.
Re message value = 5000, 5014, 5023, 5024, 5030, 5031, 5032, 5042, 5043, 5052, 5053, 5068, 5072, 5073, 5082 ...
5087, 5090, 5091, 5122 ... 5125, 5132 ... 5135, 5140:
- carry out a POWER ON (power off/on) for all components.
- check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module involved
and, if required, carry out a diagnostics routine for the faults identified.
- upgrade firmware to later version.
- contact the Hotline.
- replace the Control Unit.
Re message value = 5012:
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Module (p9810). It is
not permissible for the PROFIsafe address to be 0 or FFFF!
Re message value = 5013, 5025:
- carry out a POWER ON (power off/on) for all components.
- check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Module (p9810).
- check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module involved
and, if required, carry out a diagnostics routine for the faults identified.
Re message value = 5022:
- check the setting of the values of the F parameters at the PROFIsafe slave (F_SIL, F_CRC_Length, F_Par_Version,
F_Source_Add, F_Dest_add, F_WD_Time).
Re message value = 5026:
- check the settings of the values of the F parameters and the F parameter CRC (CRC1) calculated from these at the
PROFIsafe slave and update.
Re message value = 5065:
- check the configuration and communication at the PROFIsafe slave (cons. No. / CRC).
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module involved
and, if required, carry out a diagnostics routine for the faults identified.
Re message value = 5066:
- check the setting of the value for F parameter F_WD_Time on the PROFIsafe slave and increase if necessary.
- evaluate diagnostic information in the F host.
- check PROFIsafe connection.
586
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms