Sign-Of-Life Failure For Off In Remote; Units Changeover: Reference Parameter Value Invalid; Calculation Parameter Values After Reference Value Change Unsuccessful - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
Remedy:
Set the monitoring time higher at the PC or, if required, completely disable the monitoring function.
For the commissioning software, the monitoring time is set as follows:
<Drive> -> Commissioning -> Control panel -> Button "Fetch master control" -> A window is displayed to set the mon-
itoring time in milliseconds.
Notice:
The monitoring time should be set as short as possible. A long monitoring time means a late response when the com-
munication fails!
201031
<location>Sign-of-life failure for OFF in REMOTE
Message value:
-
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
Servo: OFF3 (ENCODER, IASC/DCBRAKE, NONE, OFF1, OFF2, STOP1, STOP2)
Infeed: OFF1 (NONE, OFF2)
Acknowledge:
IMMEDIATELY
Cause:
With the "OFF in REMOTE" mode active, no sign-of-life was received within 3 seconds.
Remedy:
- Check the data cable connection at the serial interface for the Control Unit (CU) and operator panel.
- Check the data cable between the Control Unit and operator panel.
201033
<location>Units changeover: Reference parameter value invalid
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing over the units to the referred representation type, it is not permissible for any of the required reference
parameters to be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
See also: p0349 (System of units, motor equivalent circuit diagram data), p0505 (Selecting the system of units)
Remedy:
Set the value of the reference parameter to a number different than 0.0.
See also: p0304, p0305, p0310, p2000, p2001, p2002, p2003, r2004
201034
<location>Units changeover: Calculation parameter values after reference value
change unsuccessful
Message value:
Parameter: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The change of a reference parameter meant that for an involved parameter the selected value was not able to be re-
calculated in the per unit representation. The change was rejected and the original parameter value restored.
Fault value (r0949, parameter):
Parameter whose value was not able to be re-calculated.
See also: p0304, p0305, p0310, p2000, p2001, p2002, p2003, r2004
Remedy:
Select the value of the reference parameter such that the parameter involved can be calculated in the per unit repre-
sentation.
See also: p0304, p0305, p0310, p2000, p2001, p2002, p2003, r2004
514
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0